오늘 무엇을 도와드릴까요?

Where is the project location for Vijeo Designer Runtime?

Issue:
Where is the project location for Vijeo Designer Runtime?

Product Line:
IPC, Generic PC, Vijeo Designer Runtime

Resolution:
The Vijeo Designer Runtime application is stored at <drive location set for user application>:\Program Files\Schneider Electric\Vijeo-Designer 6.2\Vijeo-Runtime\Public\Projects\

This is the location where the project is loaded from when the Runtime launches.

If this FAQ did not solve your issue, you can chat with us at chat with us or e-mail us at customer.services@se.com to create a case with our Technical Support Team.

If you are not located in North America, please contact your local Customer Care Center for assistance:

Support | Schneider Electric Global (se.com)

슈나이더 일렉트릭 Korea

자세히 알아보기
제품군
자세히 알아보기
제품군
  • 제품 문서
  • 소프트웨어 다운로드
  • 제품 선택기
  • 제품 대체 및 교체
  • 지원 및 연락처 센터
  • 영업소 검색
  • 견적 받기
  • 슈나이더 일렉트릭 커뮤니티
  • 채용
  • 회사 소개
  • 부정 행위 보고
  • 접근성
  • 뉴스룸
  • 투자자
  • Ecostruxure
  • 작업 검색
  • 블로그
  • 개인정보 취급방침
  • 쿠키 공지
  • 사용 약관
  • Change your cookie settings
  • 환경설정 센터