브랜드

슈나이더 일렉트릭 코리아 웹사이트에 방문해 주셔서 감사합니다.

슈나이더 일렉트릭 코리아 웹사이트 방문자 분들 모두 환영합니다.
		
오늘 무엇을 도와드릴까요?
Can the Square D Split Core Current Transformer (CTs) 600 V series be installed on uninsulated bus?
Issue
Installation of the Square D Split Core Current Transformer (CTs) 600 V series on uninsulated bus.

Product Line
Split Core Current Transformer (CT)
PowerLogic and ION meters

Environment
Current Transformer
Energy Meter basic metering

Cause
It is required to know the Square D Split Core Current Transformer (CTs) 600 V series specifications prior installation.
Resolution
The Square D Split Core Current Transformers (CT)  600 V Series single ratio, output 5 A in the secondary, up to 600 V, and are for indoor used. More detail on their technical specifications can be found in the attached Datasheets. See the Square D Instrument Transformer on page 41, as well as on Square D Instrument 600 Volt Class Section 6 Transformers on page 13. Open the files attached below.
The maximum voltage without additional insulation is 600 V ac. Do not apply 600 V class current transformers to circuits measuring phase-to-phase voltage greater than 600 V, unless adequate additional insulation is applied between the primary conductor and the current transformers. Square D assumes no responsibility for damage of equipment or personal injury caused by transformers operated on circuits above their published ratings.
Therefore, the split core current transformer 600 V series can be used in uninsulated bus for voltage less or equal to 600 V as said above.

슈나이더 일렉트릭 Korea

첨부 파일
Data Sheet Characteristics.pdf [49.25 KB]
Instrument Transformer.pdf [1.06 MB]
Instrument 600 Volt Class.pdf [436.84 KB]
자세히 알아보기
제품군
자세히 알아보기
제품군
  • 제품 문서
  • 소프트웨어 다운로드
  • 제품 선택기
  • 제품 대체 및 교체
  • 지원 및 연락처 센터
  • 영업소 검색
  • 견적 받기
  • 슈나이더 일렉트릭 커뮤니티
  • 채용
  • 회사 소개
  • 부정 행위 보고
  • 접근성
  • 뉴스룸
  • 투자자
  • Ecostruxure
  • 작업 검색
  • 블로그
  • 개인정보 취급방침
  • 쿠키 공지
  • 사용 약관
  • Change your cookie settings