오늘 무엇을 도와드릴까요?

What are the fan part numbers for ATV320?

The fan part numbers for the Altivar 320 (ATV320) vary depending on the specific drive model and rating.

To identify the correct fan part number:

  • Refer to the attached document, which provides a complete list of fan part numbers mapped to each ATV320 drive reference.


NOTE 1: Not all the fan kits are available for sale.  You can check with Schneider Electric Industrial Repair at 1-800-950-9550 to see if they can be specially purchased.

If this article does not answer your question, check out our FAQ database that has answers to more commonly asked questions:

Frequently Asked Questions - Schneider Electric (se.com)

If this FAQ did not solve your issue, you can call us at 1-888-778-2733 Option 2 and then 4 or e-mail us atdrive.products.support@se.comto create a case with our Technical Support Team.

If you are not located in North America, please contact your local Customer Care Center for assistance:

Support | Schneider Electric Global (se.com)

슈나이더 일렉트릭 Korea

첨부 파일
ATV320 Fan.xlsx [17.6 KB]
자세히 알아보기
제품군
자세히 알아보기
제품군
  • 제품 문서
  • 소프트웨어 다운로드
  • 제품 선택기
  • 제품 대체 및 교체
  • 지원 및 연락처 센터
  • 영업소 검색
  • 견적 받기
  • 슈나이더 일렉트릭 커뮤니티
  • 채용
  • 회사 소개
  • 부정 행위 보고
  • 접근성
  • 뉴스룸
  • 투자자
  • Ecostruxure
  • 작업 검색
  • 블로그
  • 개인정보 취급방침
  • 쿠키 공지
  • 사용 약관
  • Change your cookie settings