브랜드

슈나이더 일렉트릭 코리아 웹사이트에 방문해 주셔서 감사합니다.

슈나이더 일렉트릭 코리아 웹사이트 방문자 분들 모두 환영합니다.
		
오늘 무엇을 도와드릴까요?
How to modify runtime security setting on EOTE V3.1 with USB drive
1. Issue
How to modify runtime security setting on EOTE V3.1 with USB drive
2. Environment
EOTE V3.1
3. Resolution
  1. ) Set In the [Project Explorer], select [Security] [Setting], and click [Export].
  2. ) Define the location and file name.
Note: To import the exported file to the panel, save the file to the root directory of USB   memory with the specified folder and file name.
Folder Name:  UserManagement
File Name: data.bin
3. )   Enter the encryption key. This key is used for importing and modifying user information.
4. )   To import user information from the panel, setting up scripts is required.
5. )   On the screen, touch the import switch.
6. )   Enter the encryption key. On the panel, the project user information is overwritten.
4. FAQ Applicable Conditions
FAQ also applies to Vijeo XD V3.0.



슈나이더 일렉트릭 Korea

자세히 알아보기
제품군
자세히 알아보기
제품군
  • 제품 문서
  • 소프트웨어 다운로드
  • 제품 선택기
  • 제품 대체 및 교체
  • 지원 및 연락처 센터
  • 영업소 검색
  • 견적 받기
  • 슈나이더 일렉트릭 커뮤니티
  • 채용
  • 회사 소개
  • 부정 행위 보고
  • 접근성
  • 뉴스룸
  • 투자자
  • Ecostruxure
  • 작업 검색
  • 블로그
  • 개인정보 취급방침
  • 쿠키 공지
  • 사용 약관
  • Change your cookie settings