How can I change the relay status from NO to NC on the Altivar Process Drives?
Issue:
They need to change the function of the output relay from Normally Open contact to a Normally Closed contact.
Product line:
Altivar Process, ATV600 ATV900
Environment:
all
Cause:
The Altivar Process drives come with only R1 having a normally open and normally closed contact. R2, R3 and the extended IO Card relays are all Normally Open only.
Resolution:
Under the Relay configuration menu (i.e. R2 Configuration > go to R2 Active at. The factory setting is 1 (closed). Change this value to 0 for active when open to invert the relay output signal.
NOTE: Operating State Fault (FLT) cannot be assigned to 0. If an additional NC contact is needed for Fault indication, add an external control relay with the additional contacts.
They need to change the function of the output relay from Normally Open contact to a Normally Closed contact.
Product line:
Altivar Process, ATV600 ATV900
Environment:
all
Cause:
The Altivar Process drives come with only R1 having a normally open and normally closed contact. R2, R3 and the extended IO Card relays are all Normally Open only.
Resolution:
Under the Relay configuration menu (i.e. R2 Configuration > go to R2 Active at. The factory setting is 1 (closed). Change this value to 0 for active when open to invert the relay output signal.
NOTE: Operating State Fault (FLT) cannot be assigned to 0. If an additional NC contact is needed for Fault indication, add an external control relay with the additional contacts.
게시 대상: 슈나이더 일렉트릭 Korea






도움이 필요하신가요?
제품 선택기
애플리케이션에 적합한 제품과 액세서리를 빠르고 쉽게 찾을 수 있습니다.
견적 받기
영업 관련하여 온라인으로 문의하시면 전문가가 연락드립니다.
구매처
해당 지역의 가장 가까운 슈나이더 일렉트릭 대리점을 쉽게 찾을 수 있습니다.
지원 센터
한 곳에서 모든 요구 사항에 대한 지원 리소스를 찾아보십시오.