How can I change the relay status from NO to NC on the Altivar Process Drives?
Issue:
They need to change the function of the output relay from Normally Open contact to a Normally Closed contact.
Product line:
Altivar Process, ATV600 ATV900
Environment:
all
Cause:
The Altivar Process drives come with only R1 having a normally open and normally closed contact. R2, R3 and the extended IO Card relays are all Normally Open only.
Resolution:
Under the Relay configuration menu (i.e. R2 Configuration > go to R2 Active at. The factory setting is 1 (closed). Change this value to 0 for active when open to invert the relay output signal.
NOTE: Operating State Fault (FLT) cannot be assigned to 0. If an additional NC contact is needed for Fault indication, add an external control relay with the additional contacts.
They need to change the function of the output relay from Normally Open contact to a Normally Closed contact.
Product line:
Altivar Process, ATV600 ATV900
Environment:
all
Cause:
The Altivar Process drives come with only R1 having a normally open and normally closed contact. R2, R3 and the extended IO Card relays are all Normally Open only.
Resolution:
Under the Relay configuration menu (i.e. R2 Configuration > go to R2 Active at. The factory setting is 1 (closed). Change this value to 0 for active when open to invert the relay output signal.
NOTE: Operating State Fault (FLT) cannot be assigned to 0. If an additional NC contact is needed for Fault indication, add an external control relay with the additional contacts.
게시 대상: 슈나이더 일렉트릭 Korea





