오늘 무엇을 도와드릴까요?

How to derate an ATV930 / 950 drive for high elevation installation?

Issue:
Derating an ATV930 / 950 drive for high elevation installation.

Product Line:
Altivar 930 950

Resolution:
0...1,000m / 0...3,300ft without derating
1,000...4,800m / 3,300...15,700ft with derating
See attachment, excerpt from the Installation manual.

If this article does not answer your question, check out our FAQ database that has answers to more commonly asked questions:

Frequently Asked Questions - Schneider Electric (se.com)

If this FAQ did not solve your issue, you can call us at 1-888-778-2733 Option 2 and then 4 or e-mail us at drive.products.support@se.com to create a case with our Technical Support Team.

If you are not located in North America, please contact your local Customer Care Center for assistance:

Support | Schneider Electric Global (se.com)

슈나이더 일렉트릭 Korea

첨부 파일
ATV900 altitude.pdf [60.8 KB]
자세히 알아보기
제품군
자세히 알아보기
제품군
  • 제품 문서
  • 소프트웨어 다운로드
  • 제품 선택기
  • 제품 대체 및 교체
  • 지원 및 연락처 센터
  • 영업소 검색
  • 견적 받기
  • 슈나이더 일렉트릭 커뮤니티
  • 채용
  • 회사 소개
  • 부정 행위 보고
  • 접근성
  • 뉴스룸
  • 투자자
  • Ecostruxure
  • 작업 검색
  • 블로그
  • 개인정보 취급방침
  • 쿠키 공지
  • 사용 약관
  • Change your cookie settings
  • 환경설정 센터