브랜드

슈나이더 일렉트릭 코리아 웹사이트에 방문해 주셔서 감사합니다.

슈나이더 일렉트릭 코리아 웹사이트 방문자 분들 모두 환영합니다.
		
오늘 무엇을 도와드릴까요?
Creating an IODDT variable for BMXNOE0100
Title
IODDT variable creation

Product Line
M340 BMXNOE0100 BMXNOE0110

Environment
Unity Pro, Control Expert

Resolution
1. After adding your BMXNOE0100 to the program, double click the IO Derived Variable in the Unity Project Browser.
2. Click into the Name Cell and enter the name for your IODDT variable. for example - NOE_Status
3. Next double Click the Type Column cell
4. Click the button wit the three dots
5. The Data Editor - Variable Type selection window opens
6. Select and expand the Catalog Folder. Then expand the M340 Folder.
7. Select the Communication Folder
8. Select the T_COM_ETH_BMX IODDT and Click OK to confirm selection
9. Click the Address Column cell
10. Enter the Topological Address of the NOE. For example, %CH0.2.0
a.1. The %CH stands for Channel
b. First zero is for Rack Number
c. The Two is for the Slot Number
d. The last zero is for the Channel number
11. The BMXNOE0100 IODDT is complete. Expand to see variable elements

If this FAQ did not solve your issue, you can chat with us at chat with us or e-mail us at customer.services@se.com to create a case with our Technical Support Team.

If you are not located in North America, please contact your local Customer Care Center for assistance:
Support | Schneider Electric Global (se.com)

슈나이더 일렉트릭 Korea

  • 제품 문서
  • 소프트웨어 다운로드
  • 제품 선택기
  • 제품 대체 및 교체
  • 지원 및 연락처 센터
  • 영업소 검색
  • 견적 받기
  • 슈나이더 일렉트릭 커뮤니티
  • 채용
  • 회사 소개
  • 부정 행위 보고
  • 접근성
  • 뉴스룸
  • 투자자
  • Ecostruxure
  • 작업 검색
  • 블로그
  • 개인정보 취급방침
  • 쿠키 공지
  • 사용 약관
  • Change your cookie settings