브랜드

슈나이더 일렉트릭 코리아 웹사이트에 방문해 주셔서 감사합니다.

슈나이더 일렉트릭 코리아 웹사이트 방문자 분들 모두 환영합니다.
		
오늘 무엇을 도와드릴까요?
Can I connect an external Load Current Transformer to the Tesys T LTMR product?
Issue:
Full Load Current rating of the motor being used exceeds the rating of the LTMR.  Customer would like to connect an external load current transformer to the Tesys T to compensate.

Product line:
Tesys-T LTMR

Environment:
LTMR08*** series.

Cause:
Full Load Current of the motor being used is between 100 and 810 amps.  The built-in CT of the LTMR can measure up to 100 amps.

Resolution:
An external CT can be used with the Tesys T series.

The controller can accept 5 A and 1 A secondary signals from external current transformers. The
recommended controller model for these currents is the 0.4-8 A model. Use multiple passes through the
controller CT windows, if required.
External CTs are specified with a transformation ratio. The ratio of the external CT is the ratio of the motor
input current to the CT output current.
To activate the controller to adjust the FLC range and display the actual line current, set the following
parameters:
 Load CT Primary (the first number of the CT ratio)
 Load CT Secondary (the second number of the CT ratio)
 Load CT Multiple Passes (the number of times the CT output wires pass through the controller’s internal
CT windows.)

슈나이더 일렉트릭 Korea

자세히 알아보기
제품군
자세히 알아보기
제품군
  • 제품 문서
  • 소프트웨어 다운로드
  • 제품 선택기
  • 제품 대체 및 교체
  • 지원 및 연락처 센터
  • 영업소 검색
  • 견적 받기
  • 슈나이더 일렉트릭 커뮤니티
  • 채용
  • 회사 소개
  • 부정 행위 보고
  • 접근성
  • 뉴스룸
  • 투자자
  • Ecostruxure
  • 작업 검색
  • 블로그
  • 개인정보 취급방침
  • 쿠키 공지
  • 사용 약관
  • Change your cookie settings