브랜드

슈나이더 일렉트릭 코리아 웹사이트에 방문해 주셔서 감사합니다.

슈나이더 일렉트릭 코리아 웹사이트 방문자 분들 모두 환영합니다.
		
오늘 무엇을 도와드릴까요?
OPC Server Configuration Unchanged. No New Sources detected with Default support Error When Adding New Devices in PME


Issue
After adding a device into PME and selecting update OPC Server the user is met with "OPC Server Configuration unchanged. No New Sources detected with default support."

OPC error for custom modbus devices

Product Line
Power Monitoring Expert 7.2.2
Power Monitoring Expert 8.2


Environment
OPC Servers

Cause
The issue is caused because the device that is being added is using a custom driver. The OPC update server option is only for default native drivers.

Resolution
To resolve the issue, you must open the custom driver in the MDI (Modbus Device Importer) and follow the steps below

  1. Expand the Manager tree
  2. Right click on the module folder you wish to expose to OPC and then click on "OPC..."
  3. Select the measurements and then Click on file
  4. Under file select export.
  5. After the export go back to Management Console and click on the "Update OPC Server" again under tools


management console

This time the "Update OPC Server" option will discover the device's measurements that were previously not exposed.




슈나이더 일렉트릭 Korea

자세히 알아보기
제품군
자세히 알아보기
제품군
  • 제품 문서
  • 소프트웨어 다운로드
  • 제품 선택기
  • 제품 대체 및 교체
  • 지원 및 연락처 센터
  • 영업소 검색
  • 견적 받기
  • 슈나이더 일렉트릭 커뮤니티
  • 채용
  • 회사 소개
  • 부정 행위 보고
  • 접근성
  • 뉴스룸
  • 투자자
  • Ecostruxure
  • 작업 검색
  • 블로그
  • 개인정보 취급방침
  • 쿠키 공지
  • 사용 약관
  • Change your cookie settings