브랜드

Impact-Company-Logo-English Black-01-177x54

슈나이더 일렉트릭 코리아 웹사이트에 방문해 주셔서 감사합니다.

슈나이더 일렉트릭 코리아 웹사이트 방문자 분들 모두 환영합니다.
		
오늘 무엇을 도와드릴까요?
Unable to open the Alarms tab after upgrading to PME 9.0

Issue:
The following message is displayed when trying to open the Alarms tab from the Web Applications
after upgrading to PME 9.0.
"Alarms is processing existing records for the first time use.
The Alarms application will be ready for use once the historical processing is complete"

error

PRODUCT LINE:
Power Monitoring Expert 9.0

ENVIRONMENT:
Web Applications in Power Monitoring Expert

CAUSE:
The Alarm tab is not opening and the Progress Report shows 0% complete even after the Refresh link
is pressed several times. The diagnostic system log shows this message below.
"Could not find Stored Procedure 'dbo.CleanCorruptincidentsAndAlarms"

RESOLUTION:
*Warning: Irreparable database damage can occur. This procedure should only be performed by users familiar with
SQL Server Management Studio. Databases should be backed up prior to performing this procedure.*


*Warning: Take backups of any files prior to modifying them. Ensure the backups
are in a location that will not be overwritten (i.e. the Desktop).

Go to SQL Management Studio and run the attached SQL query to create the
'dbo.CleanCorruptincidentsAndAlarms Stored Procedure.
Once the query is run, verify the Stored Procedure is created under ION_Data\Programmability\Stored Procedures.


stored procedure

After verifying that the stored procedure has been created, restart all ION Services and check on the alarms processing progress in the Web Application Alarms tab

슈나이더 일렉트릭 Korea

첨부 파일
Create_CleanCorruptIncidentsAndAlarms.sql [2.89 KB]
자세히 알아보기
제품군
자세히 알아보기
제품군
  • 제품 문서
  • 소프트웨어 다운로드
  • 제품 선택기
  • 제품 대체 및 교체
  • 지원 및 연락처 센터
  • 영업소 검색
  • 견적 받기
  • 슈나이더 일렉트릭 커뮤니티
  • 채용
  • 회사 소개
  • 부정 행위 보고
  • 접근성
  • 뉴스룸
  • 투자자
  • Ecostruxure
  • 작업 검색
  • 블로그
  • 개인정보 취급방침
  • 쿠키 공지
  • 사용 약관
  • Change your cookie settings