오늘 무엇을 도와드릴까요?
Why are Events not being displayed in the PowerChute browser interface?
Issue:
Events are not displayed in the PowerChute browser interface.
Product:
PowerChute Business Edition versions 9.5 and above.
PowerChute Serial Shutdown
Environment:
All supported Windows OS
Cause:
Solution:
Events are not displayed in the PowerChute browser interface.
Product:
PowerChute Business Edition versions 9.5 and above.
PowerChute Serial Shutdown
Environment:
All supported Windows OS
Cause:
- Java Scripts may be blocked.
- This issue may be caused by uBlock Origin running on Firefox.
Solution:
- Allow the browser to run Java scripts and verify that the security tool allows Java scripts to run. For assistance with enabling Java scripts with your browser, see this site: https://www.enable-javascript.com/ or search on enabling Java scripts using your favorite search engine.
- To fix the issue with uBlock on Firefox, add a whitelist entry for https://localhost:6547/*
게시 대상: 슈나이더 일렉트릭 Korea