오늘 무엇을 도와드릴까요?

What is the MODBUS Register Mapping of Identity for CPUs and communication modules in M580?

Issue
Customers want to know the mapping of the Identity on CPUs and BMENOC0301/11 communication modules in M580 systems.

Product Line
Ecostruxure Control Expert, Unity Pro, M580, BMENOC0301, BMENOC0311

Environment
Control Expert v14.1, Windows 10 version 1902 (OS Build 18362.30), BMEP586040 v3.10, BMENOC0301 v2.17

Resolution
Identity data of 24 words, are availalble on CPUs and BMENOC0301/11 communication modules using Modbus function code 3 with the unit ID set to 100, offset Modbus Address 2001 and below is the MODBUS Register Mapping:
AddressMS ByteLS ByteCIP TypeComments
2001MS ByteLS ByteUINTVendor ID
Offset + 01MS ByteLS ByteUINTDevice Type
Offset + 02MS ByteLS ByteUINTProduct code
Offset + 03MS ByteLS ByteUSINTRevision – Major Revision
Not used
Offset + 04MS ByteLS ByteUSINTRevision – Minor Revision
Not used
Offset + 05MS ByteLS ByteWORDStatus
Offset + 06MSW – MSBMSW – LSBUDINTSerial Number
Offset + 07LSW – MSBLSW – LSB
Offset + 08MS ByteLS ByteWORDLength of Product Name
Not usedLengthMax of 32 characters
Offset + 09MS byte LS ByteSHORT_Product Name: Length 32 characters
CH 0CH 1STRING
Offset + 09 + 15CH 14CH 15

슈나이더 일렉트릭 Korea

자세히 알아보기
제품군
자세히 알아보기
제품군

도움이 필요하신가요?

도움이 필요하신가요?

제품 선택기

제품 선택기

애플리케이션에 적합한 제품과 액세서리를 빠르고 쉽게 찾을 수 있습니다.

견적 받기

견적 받기

영업 관련하여 온라인으로 문의하시면 전문가가 연락드립니다.

구매처

구매처

해당 지역의 가장 가까운 슈나이더 일렉트릭 대리점을 쉽게 찾을 수 있습니다.

지원 센터

지원 센터

한 곳에서 모든 요구 사항에 대한 지원 리소스를 찾아보십시오.

  • 제품 문서
  • 소프트웨어 다운로드
  • 제품 선택기
  • 제품 대체 및 교체
  • 지원 및 연락처 센터
  • 영업소 검색
  • 견적 받기
  • 슈나이더 일렉트릭 커뮤니티
  • 채용
  • 회사 소개
  • 부정 행위 보고
  • 접근성
  • 뉴스룸
  • 투자자
  • Ecostruxure
  • 작업 검색
  • 블로그
  • 개인정보 취급방침
  • 쿠키 공지
  • 사용 약관
  • Change your cookie settings