브랜드

슈나이더 일렉트릭 코리아 웹사이트에 방문해 주셔서 감사합니다.

슈나이더 일렉트릭 코리아 웹사이트 방문자 분들 모두 환영합니다.
		
오늘 무엇을 도와드릴까요?
PM8000 Front Display shows up INF value for Delivered Energy reading 'kWh del-rec', kWh, kVARh, kVAh.
Product Line
PM8000

Environment
PM8000 Front Display

Cause
PM8000 Front Display shows up INF for Delivered Energies like 'kWh del-rec' or Energy Delivered parameters like kWh, kVARh or kVAh.


Summary Display

Energy Delivered Display


Resolution
This behavior is observed when the meter's clock is set to 'Line Frequency' and meter's firmware is older than version V2.1.0. As a short term Workaround it is recommended that Source Clock set to 'Internal'.

Firmware version V2.1.0 has fixed this behavior even if the clock is set to 'Line Frequency'. Version V2.1.0 uses a new architecture and new internal storage format when performing the firmware upgrade, the meter will complete refactor the internal memory.

Then in order to get to the latest features and changes that are designed to expand the functionality of the meter, upgrade it's firmware to the latest version 3.1.0 (V003.001.000).

Here is the link how to upgrade firmware version of PM8000 to V.2.1.0: FA377135

Here is the link to the latest version 3.1.0 (V003.001.000):
https://www.se.com/ca/en/download/document/PM8000_meter_FW_v003.001.000/

슈나이더 일렉트릭 Korea

자세히 알아보기
제품군
자세히 알아보기
제품군
  • 제품 문서
  • 소프트웨어 다운로드
  • 제품 선택기
  • 제품 대체 및 교체
  • 지원 및 연락처 센터
  • 영업소 검색
  • 견적 받기
  • 슈나이더 일렉트릭 커뮤니티
  • 채용
  • 회사 소개
  • 부정 행위 보고
  • 접근성
  • 뉴스룸
  • 투자자
  • Ecostruxure
  • 작업 검색
  • 블로그
  • 개인정보 취급방침
  • 쿠키 공지
  • 사용 약관
  • Change your cookie settings