Configuration Manager Tool 2020 - Unable to Write to System - PME Portuguese Language
Issue
"Write to System" is grayed out when trying to write an archive from a "PME 2020 - language Portuguese" into a new "PME 2020 - language Portuguese" - regardless if it is distributed or standalone.

Product Line
Power Monitoring Expert 2020

Environment
Configuration Manager Tool 2020 (CM Tool 2020) - System Migration PME 2020 to PME 2020

Cause
The registry CultureInfoName in a PME system for Portuguese version is set to "pt-BR" however CMTool file that reads the supported versions is using "pt", hence the tool cannot recognize this as a supported path.

Resolution
  1. Open Configuration Manager Tool 2020 > bin > SupportedVersions.xml in a notepad (make a copy of this file just for safety).
  2. Search for Languages="pt"
  3. You will find 4 lines:
    • Line 189:       <From Version="9.1" InstallationTypes="Distributed" Languages="pt" Editions="" />
    • Line 190:       <To Version="9.1" InstallationTypes="Distributed" Languages="pt" Editions="" />
    • Line 237:       <From Version="9.1" InstallationTypes="Standalone,Distributed" Languages="pt" Editions="" />
    • Line 238:       <To Version="9.1" InstallationTypes="Standalone,Distributed" Languages="pt" Editions="" />
  4. Replace it for Languages="pt-BR"
  5. Save it.

슈나이더 일렉트릭 Korea

자세히 알아보기
제품군
자세히 알아보기
제품군
  • 제품 문서
  • 소프트웨어 다운로드
  • 제품 선택기
  • 제품 대체 및 교체
  • 지원 및 연락처 센터
  • 영업소 검색
  • 견적 받기
  • 슈나이더 일렉트릭 커뮤니티
  • 채용
  • 회사 소개
  • 부정 행위 보고
  • 접근성
  • 뉴스룸
  • 투자자
  • Ecostruxure
  • 작업 검색
  • 블로그
  • 개인정보 취급방침
  • 쿠키 공지
  • 사용 약관
  • Change your cookie settings