브랜드

슈나이더 일렉트릭 코리아 웹사이트에 방문해 주셔서 감사합니다.

슈나이더 일렉트릭 코리아 웹사이트 방문자 분들 모두 환영합니다.
		
오늘 무엇을 도와드릴까요?
Integrity check error is returned after running Control Expert following GPL Library install
Issue
Integrity check error is returned after running Control Expert following 'PSx GPL 2015 R2 for Unity Pro' Library install

Product Line
Control Expert

Environment
Windows 10.

Resolution
An integrity check error message gets returned after starting Control Expert 14.1 following the installation of the
'PSx GPL 2015 R2 for Unity Pro' library.

The issue can be resolved by performing the following steps:
  • Uninstall Control Expert 14.1
  • Reboot.
  • Delete the folder named ‘PSx GPL for Unity Pro’ from the folder named ‘C:\ProgramData\Schneider Electric\Control Expert 14.1'.  (Note: This folder does not get deleted by the uninstall, If a third party library is installed)
  • Install Control Expert 14.1
  • Install the hotfixes including HF1 (run Control Expert and close after each hot fix install.)
  • Install the ‘GPL_Communication’ family.
  • Run Control Expert 14.1
  • Close Control Expert14.1
  • Install the ‘GPL_Devices’ family.
  • Run Control Expert 14.1
  • Close Control Expert14.1
  • Install the ‘GPL_Diagnostics’ family.
  • Run Control Expert 14.1
  • Close Control Expert 14.1
  • Install the ‘GPL_Process’ family.
  • Run Control Expert 14.1
Note:

When you uninstall Control Expert, it should delete 'Control Expert 14.1 folder from both 'C:\ProgramData\Schneider Electric'  and
C:\Program Files (x86)\Schneider Electric.  If it doesn't, then you will need to manually delete them.

슈나이더 일렉트릭 Korea

자세히 알아보기
제품군
자세히 알아보기
제품군
  • 제품 문서
  • 소프트웨어 다운로드
  • 제품 선택기
  • 제품 대체 및 교체
  • 지원 및 연락처 센터
  • 영업소 검색
  • 견적 받기
  • 슈나이더 일렉트릭 커뮤니티
  • 채용
  • 회사 소개
  • 부정 행위 보고
  • 접근성
  • 뉴스룸
  • 투자자
  • Ecostruxure
  • 작업 검색
  • 블로그
  • 개인정보 취급방침
  • 쿠키 공지
  • 사용 약관
  • Change your cookie settings