브랜드

슈나이더 일렉트릭 코리아 웹사이트에 방문해 주셔서 감사합니다.

슈나이더 일렉트릭 코리아 웹사이트 방문자 분들 모두 환영합니다.
		
오늘 무엇을 도와드릴까요?
How to change the log off delay of the PowerChute Business Edition web page?
Issue:
The log off delay of the PowerChute Business Edition web page is to short or too long.

Product:
PowerChute Business Edition version 10

Environment:
All supported OS

Cause:
Informational

Solution:

For Windows OS when installed to the default page
Go to C:\Program Files (x86)\APC\PowerChute Business Edition\agent\etc and save the file webdefault.xml to Saved-webdefault.xml Once the file has been saved open webdefault.xml with a text editor. Search for the line session-timeout.

<session-timeout>15</session-timeout>

Change the 15 to the timeout you would like and save the file. Example: change 15 to 30 for the timeout to equal 30 minutes. Then open a command prompt as an administrator and enter the command net stop apcpbeagent Wait for the service to stop then enter net start apcpbeagent and the service will restart. The new timeout delay will now be in affect.

For Linux OS when installed to the default path
Go to /opt/APC/PowerChute Business Edition/agent/etc and save the file webdefault.xml to Saved-webdefault.xml Once the file has been saved open webdefault.xml with a text editor. Search for the line session-timeout.

<session-timeout>15</session-timeout>

Change the 15 to the timeout you would like and save the file. Example: change 15 to 30 for the timeout to equal 30 minutes. Then restart the PowerChute service. The command is sudo systemctl restart PBEAgent

슈나이더 일렉트릭 Korea

자세히 알아보기
제품군
자세히 알아보기
제품군
  • 제품 문서
  • 소프트웨어 다운로드
  • 제품 선택기
  • 제품 대체 및 교체
  • 지원 및 연락처 센터
  • 영업소 검색
  • 견적 받기
  • 슈나이더 일렉트릭 커뮤니티
  • 채용
  • 회사 소개
  • 부정 행위 보고
  • 접근성
  • 뉴스룸
  • 투자자
  • Ecostruxure
  • 작업 검색
  • 블로그
  • 개인정보 취급방침
  • 쿠키 공지
  • 사용 약관
  • Change your cookie settings