How to do a factory reset using SoMove for the Altivar Process Drives?
Issue:
Can I do a factory reset on the Altivar Process drive using SoMove Software?
Product Line:
ATV630 ATV930
Environment:
All serial numbers, all model numbers
Cause:
Customer had SoMove connection to the drive, and he wanted to use SoMove for factory reset.
Resolution:
Go to the Device tab on top of SoMove, select Factory Setting then choose Customize or Execute.

For Customize: select OEM or Schneider Electric factory settings and click OK. (Use OEM if directed by the equipment supplier).

For Execute: select All parameters or other options such as Drive configuration, Motor Control, Communications, Display Configurations and click apply.

You will have to acknowledge the Warning making sure you understand the risk before the Factory reset will be performed.

When the reset is complete you should see this dialog box:
Can I do a factory reset on the Altivar Process drive using SoMove Software?
Product Line:
ATV630 ATV930
Environment:
All serial numbers, all model numbers
Cause:
Customer had SoMove connection to the drive, and he wanted to use SoMove for factory reset.
Resolution:
Go to the Device tab on top of SoMove, select Factory Setting then choose Customize or Execute.
For Customize: select OEM or Schneider Electric factory settings and click OK. (Use OEM if directed by the equipment supplier).
For Execute: select All parameters or other options such as Drive configuration, Motor Control, Communications, Display Configurations and click apply.
You will have to acknowledge the Warning making sure you understand the risk before the Factory reset will be performed.
When the reset is complete you should see this dialog box:
게시 대상: 슈나이더 일렉트릭 Korea
도움이 필요하신가요?
제품 선택기
애플리케이션에 적합한 제품과 액세서리를 빠르고 쉽게 찾을 수 있습니다.
견적 받기
영업 관련하여 온라인으로 문의하시면 전문가가 연락드립니다.
구매처
해당 지역의 가장 가까운 슈나이더 일렉트릭 대리점을 쉽게 찾을 수 있습니다.
지원 센터
한 곳에서 모든 요구 사항에 대한 지원 리소스를 찾아보십시오.