오늘 무엇을 도와드릴까요?
What are the syslog messages on BMENOC03x1 module?
Issue
Customer wants to know what are the syslog message list generated by the BMENOC03x1 module.
Product Line
BMENOC0301, BMENOC0311
Environment
Firmware 2.17
Resolution
The "BMENOC03x1 syslog messages – V2.pdf" document contains the Syslog messages generated by the BMENOC03x1 and sent to a syslog server.
Here is below the legend to read the document (extract from the document: Modicon Controllers Platform - Cyber Security - Reference Manual: EIO0000001999.06)
Syslog message facility values as per RFC 5424 specification associated with events type:
Syslog message severity values as per RFC 5424 specification associated with events type:
Customer wants to know what are the syslog message list generated by the BMENOC03x1 module.
Product Line
BMENOC0301, BMENOC0311
Environment
Firmware 2.17
Resolution
The "BMENOC03x1 syslog messages – V2.pdf" document contains the Syslog messages generated by the BMENOC03x1 and sent to a syslog server.
Here is below the legend to read the document (extract from the document: Modicon Controllers Platform - Cyber Security - Reference Manual: EIO0000001999.06)
Events Logged
Syslog message structure:| Field | Description |
| PRI | Facility and severity information (description provided in following tables). |
| VERSION | Version of the syslog protocol specification (Version = 1 for RFC 5424.). |
| TIMESTAMP | Time stamp format is issued from RFC 3339 that recommends the following ISO8601 Internet date and time format: YYY-MM-DDThh:mm:ss.nnnZ NOTE: -, T, :, . , Z are mandatory characters and they are part or the time stamp field. T and Z need to be written in uppercase. Z specifies that the time is UTC. Time field content description: YYY Year MM Month DD Day hh Hour mm Month ss Second nnn Fraction of second in millisecond (0 if not available) |
| HOSTNAME | Identifies the machine that originally sent the syslog message: fully qualified domain name (FQDN) or source static IP address if FQDN is not supported. |
| APP-NAME | Identifies the application that initiates the syslog message. It contains information that allows to identify the entity that sends the message (for example, subset of commercial reference). |
| PROCID | Identifies the process, or entity, or component that sends the event. Receives NILVALUE if not used. |
| MSGID | Identifies the type of message on which the event is related to, for example HTTP, FTP, Modbus. Receives NILVALUE if not used. |
| MESSAGE TEXT | This field contains several information:
|
Syslog message facility values as per RFC 5424 specification associated with events type:
| Facility value | Description |
| 0 | Kernel messages. |
| 1 | User-level messages. |
| 2 | Mail system. |
| 3 | System daemons. |
| 4 | Security / authorization messages. |
| 5 | Messages generated internally by syslog. |
| 6 | Line printer subsystem. |
| 7 | Network news subsystems. |
| 8 | UUCP subsystem |
| 9 | Clock daemon. |
| 10 | Security / authorization messages. |
| 11 | FTP daemon. |
| 12 | NTP subsystem. |
| 13 | Log audit. |
| 14 | Log alert. |
| 15 | Clock daemon. |
| 16...23 | Local use 0...7. |
Syslog message severity values as per RFC 5424 specification associated with events type:
| Severity value | Keyword | Description |
| 0 | Emergency | System is unusable. |
| 1 | Alert | Action must be taken immediately. |
| 2 | Critical | Critical conditions. |
| 3 | Error | Error conditions. |
| 4 | Warning | Warning conditions. |
| 5 | Notice | Normal but significant condition. |
| 6 | Informational | Informal messages. |
| 7 | Debug | Debug-level messages. |
게시 대상: 슈나이더 일렉트릭 Korea