How can I setup Java to access webpage of STB under Win10/7 OS ?

1.Issue

How can I setup Java to access webpage of STB under Win10/7 OS ?

2.Environment

Windows 10 ,Windows 7,  32bit or 64bit

3.Resolution

User could install jre-8u202-windows-i586.exe for Win7 and Win10 OS and remove other Java versions from control panel.

The installation file could be downloaded in
https://www.oracle.com/java/technologies/javase/javase8-archive-downloads.html
After installation of Java ,  the security level should be selelcted to High and the webpage address of STB should be added to execption site


JAVA setting

The webpage of STB should be opened by Internet Explorer and user should choose later option when Java update needed window pops up .

java diag

User needs to accept the security warning and click run button when this window appears .

Web security
The default HTTP feature of STB NIM has been disabled due to cybersecurity enhancement if the firmware version of manufactured module is listed  as following
STBNIP2311 SV>=5.0
STBNIC2212 SV>=4.0
STBNIP2212 SV>=4.0

User could install latest Advantys configuration tool ,enable the HTTP feature in module options ,then online the STB to download the configuration.
The download link for Advantys configuration tool is  ​​​​​https://www.se.com/ww/en/search/STBSPU1000_Software

http feature selection

슈나이더 일렉트릭 Korea

자세히 알아보기
제품군
자세히 알아보기
제품군
  • 제품 문서
  • 소프트웨어 다운로드
  • 제품 선택기
  • 제품 대체 및 교체
  • 지원 및 연락처 센터
  • 영업소 검색
  • 견적 받기
  • 슈나이더 일렉트릭 커뮤니티
  • 채용
  • 회사 소개
  • 부정 행위 보고
  • 접근성
  • 뉴스룸
  • 투자자
  • Ecostruxure
  • 작업 검색
  • 블로그
  • 개인정보 취급방침
  • 쿠키 공지
  • 사용 약관
  • Change your cookie settings