브랜드

슈나이더 일렉트릭 코리아 웹사이트에 방문해 주셔서 감사합니다.

슈나이더 일렉트릭 코리아 웹사이트 방문자 분들 모두 환영합니다.
		
오늘 무엇을 도와드릴까요?
PME - When customizing the flag colors in Vista for the Numeric Objects displays and communication status, the Web Diagrams will not reflect the change.

Issue
When customizing the flag colors in Vista (Options > Flag Colors) for the Numeric Objects displays and communication status, the Web Diagrams will not reflect the change.
In Vista:
11

In Web Diagrams:
22

Product Line
Power Monitoring Expert 9.0
Power Monitoring Expert 2020 (CU2)

Environment
Vista/Web Diagrams

Cause
The flag colors in Vista is a global setting and it works separately from the diagrams.

Resolution
1) Open the file realtime.js located at  %\Power Monitoring Expert\Applications\WebReach\Scripts with a HTML editor (or notepad)
2) Make a backup copy for safety
3) The flag colors are defined as below:

Line 934:         DiagramManager.m_HiHiFlagColor = "#ff0000"; // red
Line 935:         DiagramManager.m_HighFlagColor = "#ff8000"; // orange
Line 936:         DiagramManager.m_LowFlagColor = "#00b8ff"; // light blue
Line 937:         DiagramManager.m_LoLoFlagColor = "#0000ff"; // blue
Line 938:         DiagramManager.m_ErrorFlagColor = DiagramManager.m_HighFlagColor;
Line 938:         DiagramManager.m_ErrorFlagColor = DiagramManager.m_HighFlagColor;
Line 939:         DiagramManager.m_StaleFlagColor = "#ffff00"; // yellow

4) Use an HTML color code ( https://htmlcolorcodes.com/) and change codes to reflect the ones chosen in Vista
5) Save the file and refresh Web Diagrams

Please note that all Numeric Objects will be affected as well the colors for the communication status, as the stale and error.
Vista will not be affected.

슈나이더 일렉트릭 Korea

  • 제품 문서
  • 소프트웨어 다운로드
  • 제품 선택기
  • 제품 대체 및 교체
  • 지원 및 연락처 센터
  • 영업소 검색
  • 견적 받기
  • 슈나이더 일렉트릭 커뮤니티
  • 채용
  • 회사 소개
  • 부정 행위 보고
  • 접근성
  • 뉴스룸
  • 투자자
  • Ecostruxure
  • 작업 검색
  • 블로그
  • 개인정보 취급방침
  • 쿠키 공지
  • 사용 약관
  • Change your cookie settings