Can you download a different version of SoMove Configuration file in Altivar Process VFD?
Issue:
Can SoMove Software download an older Configuration file in to the VFD?
Product Line:
ATV630 , ATV930
Environment:
Altivar
Resolution:
You can download a SoMove Conf with version N to a drive with version N or N+1 or greater. but you can't transfer it to a drive with version N-1 or less.
You have 2 solutions inthe example below:
1. You can modify the version of the offline conf, by changing the Topology.

Then click ok when SoMove displays message.

After that, transfer the conf with version V2.2 to a drive with version V2.2.
Or
2. Update the drive to the version V3.1 before transfer. Then you can perform conf transfer.