Control Expert returns 'Failed to find a valid license' after activation of a floating license..

Control Expert returns 'Failed to find a valid license' after activation of a floating license..

Examination of the file named 'License Manager_reg' shows:

ERROR: Failed to load TS, try to repair TS segment
ERROR: Failed to create transaction handle: Error: 51401
Found 1 fulfillments in Trusted Storage


The issue occurred due to the trusted storage in the PC to have been broken and the self-healing mechanism of the LMBrick is not able to fix it.

The solution would be to delete the trusted storage files and activate then all licenses again.

Use the following steps to delete the trusted license (Note: All license data on a PC are stored in the trusted storage files. By removing those files all licenses on a PC will get lost.)

  • Open the Schneider Electric License Manager (LM).
  • Record the Activation ID and part number..
  • Select the and click on the Floating license checkbox.
  • Click on 'Return' to return the license.

cv

  • Open the folder named 'C:\ProgramData\FLEXnet'.
  • Delete the files named:
    • schneide_0098df00_tsf.data
    • schneide_8098df00_tsf.data
    • schneide_0098df00_event.log
    • schneide_8098df00_event.log
    • schneide_0098df00_tsf.data_backup.001
    • schneide_8098df00_tsf.data_backup.001.

sfvv

  • Reactivate the Floating license.

슈나이더 일렉트릭 Korea

자세히 알아보기
제품군
자세히 알아보기
제품군
  • 제품 문서
  • 소프트웨어 다운로드
  • 제품 선택기
  • 제품 대체 및 교체
  • 지원 및 연락처 센터
  • 영업소 검색
  • 견적 받기
  • 슈나이더 일렉트릭 커뮤니티
  • 채용
  • 회사 소개
  • 부정 행위 보고
  • 접근성
  • 뉴스룸
  • 투자자
  • Ecostruxure
  • 작업 검색
  • 블로그
  • 개인정보 취급방침
  • 쿠키 공지
  • 사용 약관
  • Change your cookie settings