How to reduce motor noise when driven by an ATV320?
Issue:
The motor is quite noisy while running
Product Line:
ATV320
Environment:
ATV320 all series
Cause:
ATV320 is creating too much motor noise.
Resolution:
Options include:
Set noise reduction (nrd) to yes. This creates a random frequency modulation which helps prevent a resonance.
Conf > FuLL > drC- > nrd = YES
Increase the switching frequency (SFr). This may also increase the heat generated by the drive.
Conf > FuLL > drC- > SFr: (there is a range between 2 to 16kHz depending on the drive size).
Consider mounting characteristics to a machine. Use mechanical joints (silent block) between the motor and the frame of the machine. It will help to suppress low frequency vibrations.
The motor is quite noisy while running
Product Line:
ATV320
Environment:
ATV320 all series
Cause:
ATV320 is creating too much motor noise.
Resolution:
Options include:
Set noise reduction (nrd) to yes. This creates a random frequency modulation which helps prevent a resonance.
Conf > FuLL > drC- > nrd = YES
Increase the switching frequency (SFr). This may also increase the heat generated by the drive.
Conf > FuLL > drC- > SFr: (there is a range between 2 to 16kHz depending on the drive size).
Consider mounting characteristics to a machine. Use mechanical joints (silent block) between the motor and the frame of the machine. It will help to suppress low frequency vibrations.