브랜드

슈나이더 일렉트릭 코리아 웹사이트에 방문해 주셔서 감사합니다.

슈나이더 일렉트릭 코리아 웹사이트 방문자 분들 모두 환영합니다.
		
오늘 무엇을 도와드릴까요?
Is it possible to monitor the Ethernet Port Status of an HMIST6 in EcoStruxure Operator Terminal Expert
Issue:
Looking for an internal system variable that will reveal the status of the Ethernet port of an HMIST6

Product Line:
Harmony HMI, HMIST6, HMISTM6, EcoStruxure Operator Terminal Expert

Resolution:
Currently in EcoStruxure Operator Terminal Expert V3.2 SP1, there is no way to determine the status of the Ethernet port by the means of a built-in  Internal System Variable.

As a workaround, we could monitor the Quality property of an External Variable. Here are the different states that the Quality property could be in:

ValueDescription
0, 4

Access to device address and device address value is normal.

1, 3, 5, 7

Cannot access the device address.

8, 12

Device address value is invalid.

9, 13, 15

You cannot access the device address. Also, the device address value can be invalid.

2, 6, 10, 11, 14

Not in use



Here is an example script that will write the Quality property to a variable named "StatusVar". Note Var1 is our external variable.

blockly

슈나이더 일렉트릭 Korea

자세히 알아보기
제품군
자세히 알아보기
제품군
  • 제품 문서
  • 소프트웨어 다운로드
  • 제품 선택기
  • 제품 대체 및 교체
  • 지원 및 연락처 센터
  • 영업소 검색
  • 견적 받기
  • 슈나이더 일렉트릭 커뮤니티
  • 채용
  • 회사 소개
  • 부정 행위 보고
  • 접근성
  • 뉴스룸
  • 투자자
  • Ecostruxure
  • 작업 검색
  • 블로그
  • 개인정보 취급방침
  • 쿠키 공지
  • 사용 약관
  • Change your cookie settings