오늘 무엇을 도와드릴까요?

What does the diagnosis LED ON mean on TeSys Giga contactors ? How many on/off operations left after the LED is ON ?

The diagnostic LED shall be ON,
  1. when the contactor (switching module) reaches its end of life, means it have reached 85% of its electrical life. The electrical life depends on the operational voltage and current, utilisation category, make break current (AC3/AC3e) and depends on application type. So, the remaining number of operations shall also vary depending on multiple factors : 1 beat
  2. Coil undervoltage (A1-A2 <0.8Uc): 2 beats
  3. Coil overvoltage (A1-A2 )1.1Uc): 3 beats
  4. Internal fault: continuous beats
  5. Remote wear diagnosis (RWD) module (only when Advanced version) cannot enable remote alarm for central monitoring: 4 beats
Note that detail information refers to installation guide DOCA0189EN and here is the link: TeSys Giga Series - Contactors and Electronic Overload Relays - Installation Guide User guide | Schneider Electric

슈나이더 일렉트릭 Korea

  • 제품 문서
  • 소프트웨어 다운로드
  • 제품 선택기
  • 제품 대체 및 교체
  • 지원 및 연락처 센터
  • 영업소 검색
  • 견적 받기
  • 슈나이더 일렉트릭 커뮤니티
  • 채용
  • 회사 소개
  • 부정 행위 보고
  • 접근성
  • 뉴스룸
  • 투자자
  • Ecostruxure
  • 작업 검색
  • 블로그
  • 개인정보 취급방침
  • 쿠키 공지
  • 사용 약관
  • Change your cookie settings