What is the MTBF of the BMENUA0100?
Product Line
- BMENUA0100
Environment
The MTBF values are provided for different operating temperatures and cycles (continuous or intermittent operation).
Resolution
The MTBF of the BMENUA0100 coupler is :
| Operating Condition | MTBF (hours) |
|---|---|
| 30°C continuous operation | 1 331 000 |
| 30°C intermittent operation | 1 191 000 |
| 60°C continuous operation | 762 440 |
| 60°C intermittent operation | 809 500 |
| 85°C continuous operation | 429 400 |
| 85°C intermittent operation | 547 600 |