How to perform an Auto-Diagnostics Test on an ATV61 or ATV71 Drive?

Resolution:
The ATV61/ATV71 drives include a built-in diagnostics feature that allows you to test internal components, such as IGBTs and thyristors. This is useful when troubleshooting issues like short circuit faults or verifying the health of the drive.

Run the auto-diagnostics test if you experience:

  • Short circuit faults
  • Suspected internal component failure
  • Unexplained drive behavior

1.- Access the Diagnostics Menu

  • Navigate to: Menu 1.10 – DIAGNOSTICS

Navigation to Menu 1.10- Diagnostics
2.- Select Test Procedures

  • Choose “Test Procedures” from the menu
  • Select the specific test you want to run

3.- Start the Test

  • A warning message will appear
  • Press and hold the ENT (Enter) key for 2 seconds to begin


Navigation to select procedure and start the test.
4.- Understanding Test Results

For each IGBT tested, results are displayed on two lines:

  • Line 1: Indicates if a short circuit is detected
  • Line 2: Indicates if the component is open (no continuity)

Technical note:
The [TEST THYRISTORS] option is only available for:

  • ATV61 drives ≥ 18.5 kW (M3 and N4 ranges)
  • All ATV61...Y models

Extended test results (Thyristors 4–12 and IGBTs 1B–6B) are only available for:

  • ATV61EC90N4 to M14N4
  • ATV61EM15Y to M24Y

If this article does not answer your question, check out our FAQ database that has answers to more commonly asked questions:

Frequently Asked Questions - Schneider Electric (se.com)

If this FAQ did not solve your issue, you can call us at 1-888-778-2733 Option 2 and then 4 or e-mail us atdrive.products.support@se.comto create a case with our Technical Support Team.

If you are not located in North America, please contact your local Customer Care Center for assistance:

Support | Schneider Electric Global (se.com)

슈나이더 일렉트릭 Korea

자세히 알아보기
제품군
자세히 알아보기
제품군
  • 제품 문서
  • 소프트웨어 다운로드
  • 제품 선택기
  • 제품 대체 및 교체
  • 지원 및 연락처 센터
  • 영업소 검색
  • 견적 받기
  • 슈나이더 일렉트릭 커뮤니티
  • 채용
  • 회사 소개
  • 부정 행위 보고
  • 접근성
  • 뉴스룸
  • 투자자
  • Ecostruxure
  • 작업 검색
  • 블로그
  • 개인정보 취급방침
  • 쿠키 공지
  • 사용 약관
  • Change your cookie settings
  • 환경설정 센터