What is the recommended RPI setting when using a BMECXM0100 CANopen Master


Issue

How should the Ethernet Requested Packet Interval (RPI) be configured when a BMECXM0100 CANopen master coupler is deployed as a Distributed I/O (DIO) device?

Product Line

  • BMECXM0100 CANopen Master Coupler

Environment

  • BMECXM0100 configured as a DIO device
  • Ethernet DIO Scanner
  • Modicon M580 CPU with MAST task configured in Cyclic or Periodic mode

Resolution

When the BMECXM0100 is used as a DIO device, configure the DIO Scanner Ethernet RPI to be at least two times faster than the CPU MAST task period.

The MAST task can be configured in either:

  • Cyclic mode
  • Periodic mode

The RPI is configured through the BMECXM0100 DTM.

When configuring the RPI, ensure that the resulting traffic does not exceed the maximum bandwidth supported by the scanner Ethernet port.

If the available DIO Scanner bandwidth is insufficient for the required update rate, deploy the BMECXM0100 behind a second Ethernet coupler.

 