How to upload and convert a Modicon Micro 110CPU612xx Modsoft application to Unity.

Use the following steps to upload the application using Modsoft:

  • Start Modsoft.
  • Click on Transfer
  • Select 'PLC to File'.
  • Select 'New Program'.

image.png

  • Type in a filename.
  • Hit ENTER

image.png

  • Type in a location for saving the application or just use the default location.
  • Hit ENTER

image.png

  • Type in the Modbus address.
  • Hit Enter.

image.png


  • Select the Modbus I

image.png


  • Select RTU for the mode.

image.png


  • Select Even for the parity

image.png


  • Select the Stop Bit.

image.png


  • Select the baud rate.

image.png


  • Select the appropriate COM port on the PC.
    • Wait for the upload to finish.
    • Save the changes.

    image.png


    • Start
    • Open the application with Unity using the 'Modsoft projects' selection.
    • Save the Unity application.

    image.png

    image.png

    • Select the PLC type to convert to:
    • Click on OK.

    image.png