SRT UPS Battery "Replace By" Date Not Updating
Problem: The battery "Replace By" date is not updating even after replacing the batteries in the UPS or a connected battery pack.
Product line: UPS models with SRT prefix
Note: This does not apply to SRTL3KRM1UC UPS models, or UPS models with SRTG prefix
Environment: All models, all serial numbers
Resolution:
For UPS systems with no external battery packs connected:
Note: This article will be updated at a later date to cover UPS systems with battery packs connected.
If the issue persists after performing the steps outlined above, please contact your local APC Technical Support and provide the following information:
Product line: UPS models with SRT prefix
Note: This does not apply to SRTL3KRM1UC UPS models, or UPS models with SRTG prefix
Environment: All models, all serial numbers
Resolution:
For UPS systems with no external battery packs connected:
- Disconnect the battery that is reporting an inaccurate "Replace By" date.
- Wait until the UPS LCD displays a "Battery Disconnected" event.
- Reconnect the battery. The UPS will prompt an acknowledgement message, and will require to confirm if the reconnected battery is new. Select Yes.
- Wait for 15 minutes and verify that the battery Install date and "Replace By" date have updated accordingly.
Note: This article will be updated at a later date to cover UPS systems with battery packs connected.
If the issue persists after performing the steps outlined above, please contact your local APC Technical Support and provide the following information:
- UPS Time: use the UPS LCD to navigate to Main Menu -> About -> UPS -> UPS Time
- RBC Summary: use the UPS LCD to navigate to Main Menu -> Status -> Battery -> RBC Summary
게시 대상: 슈나이더 일렉트릭 Korea


도움이 필요하신가요?
제품 선택기
애플리케이션에 적합한 제품과 액세서리를 빠르고 쉽게 찾을 수 있습니다.
견적 받기
영업 관련하여 온라인으로 문의하시면 전문가가 연락드립니다.
구매처
해당 지역의 가장 가까운 슈나이더 일렉트릭 대리점을 쉽게 찾을 수 있습니다.
지원 센터
한 곳에서 모든 요구 사항에 대한 지원 리소스를 찾아보십시오.