How to get the firmware version of an ethernet communication module (BMENOCxxx) ?
If the firmware has never been updated since it has been manufactured, the SV marked on the product shows the firmware release set inside the module.
Otherwise, there are three methods for getting the firmware release of an ethernet communication module in a Mx80 rack :
1 : By connecting Control-Expert to the CPU :
b : the parameter "FIRMWARE_VERSION" is set with the value of the firmware version in hexadecimal (high byte: Major version; Low byte: Minor version) => in the example below, version 2.19 is displayed
2 : By using the Unity-Loader tool with the BMENOCxyz device :
b : the firmware release is displayed on the right window as shown below (version 2.19 in our example) :
3 : By using the EADM (EcoStruxure Automation Device Maintenance) tool with the device BMENOCxyz :
b : Select the package (*.ldx file) available in the "Data Package" folder :
c : Click on the icon to enter the Firmware password and click on Connect => the firmware version of the device appears in the box (in this example, 2.19)
게시 대상: 슈나이더 일렉트릭 Korea
도움이 필요하신가요?
제품 선택기
애플리케이션에 적합한 제품과 액세서리를 빠르고 쉽게 찾을 수 있습니다.
견적 받기
영업 관련하여 온라인으로 문의하시면 전문가가 연락드립니다.
구매처
해당 지역의 가장 가까운 슈나이더 일렉트릭 대리점을 쉽게 찾을 수 있습니다.
지원 센터
한 곳에서 모든 요구 사항에 대한 지원 리소스를 찾아보십시오.