오늘 무엇을 도와드릴까요?

PowerChute Network Shutdown is unable to shut down and start up Nutanix Files VMs via SSH when vCenter is offline if on a different subnet than Nutanix Files VMs

Issue:
PowerChute Network Shutdown is unable to shut down and start up Nutanix Files VMs via SSH when vCenter is offline if vCenter is on a different network subnet than the Nutanix Files VMs

Products:
PowerChute Network Shutdown v4.x

Environment:
PowerChute configured with Nutanix support with VMware as hypervisor
vCenter Server deployed as a VM outside or inside of the Nutanix Cluster
Nutanix Files version 3.8.1.1

Solution:
Deploy PowerChute Network Shutdown on the same subnet as the Nutanix Files VMs or modify the firewall rules on the Nutanix Files VMs to allow SSH connection from PowerChute (not recommended).

슈나이더 일렉트릭 Korea

  • 제품 문서
  • 소프트웨어 다운로드
  • 제품 선택기
  • 제품 대체 및 교체
  • 지원 및 연락처 센터
  • 영업소 검색
  • 견적 받기
  • 슈나이더 일렉트릭 커뮤니티
  • 채용
  • 회사 소개
  • 부정 행위 보고
  • 접근성
  • 뉴스룸
  • 투자자
  • Ecostruxure
  • 작업 검색
  • 블로그
  • 개인정보 취급방침
  • 쿠키 공지
  • 사용 약관
  • Change your cookie settings