How can you program a Jog function, in a ATV212 drive?
Issue:
Programming a Jog function, in a ATV212 drive.
Product Line:
ATV212
Environment:
Jog
Cause:
n/a
Resolution:
This drive does not have a jog function, in the menus. You would need to program a Preset Speed. Go to F113 (RES) and set to 6 and set SR1 to 10 ( or whatever jog speed you need?). When F and RES goes high, should run at the jog speed.
게시 대상: 슈나이더 일렉트릭 Korea

