Can a Modicon M238 controller store the SoMachine source code?

Yes, M238 Modicon controllers have the capability to store the SoMachine source code.

- To download the source code to the M238, the M238 will have to be in Stop mode. After that go to the Logic Builder menu / File / Source download.
- To upload the source code from the M238, the M238 will also need to be in Stop mode. If the PLC is Run mode, the message "No source archive available on the plc" will be displayed when the upload is performed from either Logic Builder menu / FIle / Source download (when offline) or from SoMachine Central / Connect controller.

Important note: The M238 does not have a Start/Stop switch and the only way to stop the PLC is to connect to the PLC with any project. That presents the risk, that if no source code is on the PLC, the existing program that is stored in flash (the compiled code, loaded to RAM on power-up) will be overwritten. If the source code is available, that can be used to generate the compiled code to download to the PLC.

M238 is an obsolete product.

If this FAQ did not solve your issue, you can chat with us at chat with us or e-mail us at customer.services@se.com to create a case with our Technical Support Team.

If you are not located in North America, please contact your local Customer Care Center for assistance:
Support | Schneider Electric Global (se.com)

슈나이더 일렉트릭 Korea

자세히 알아보기
제품군
자세히 알아보기
제품군

도움이 필요하신가요?

도움이 필요하신가요?

제품 선택기

제품 선택기

애플리케이션에 적합한 제품과 액세서리를 빠르고 쉽게 찾을 수 있습니다.

견적 받기

견적 받기

영업 관련하여 온라인으로 문의하시면 전문가가 연락드립니다.

구매처

구매처

해당 지역의 가장 가까운 슈나이더 일렉트릭 대리점을 쉽게 찾을 수 있습니다.

지원 센터

지원 센터

한 곳에서 모든 요구 사항에 대한 지원 리소스를 찾아보십시오.

  • 제품 문서
  • 소프트웨어 다운로드
  • 제품 선택기
  • 제품 대체 및 교체
  • 지원 및 연락처 센터
  • 영업소 검색
  • 견적 받기
  • 슈나이더 일렉트릭 커뮤니티
  • 채용
  • 회사 소개
  • 부정 행위 보고
  • 접근성
  • 뉴스룸
  • 투자자
  • Ecostruxure
  • 작업 검색
  • 블로그
  • 개인정보 취급방침
  • 쿠키 공지
  • 사용 약관
  • Change your cookie settings