오늘 무엇을 도와드릴까요?

Redundancy communications on SAGE 3030M

Issue: The Sage RTU 3030M has two ethernet ports available, is there a way to use this two ports for a redundancy communication with the RTU, in case one connection fails, take advantage of the other.

Product Line: Sage RTU Devices

Environment: Industrial communication networks and protocols

Cause: Lack of information about this configuration in the corresponding manuals.

Resolution: The two ethernet ports are independent of each other, so you can assign each socket to a particular ethernet interface (primary vs secondary RJ45 connector). It is necessary to create a different socket, program it with the desire protocol and then you will have two independent comm paths to the RTU.

Notice that, if using ethernet, creating a 2nd socket is not enough to create redundant communication path if using the same ethernet interface, as that is a single point of failure. If a switch or router goes down, both the main and the redundant comm paths are taken down. DNPR also has the comm associations feature (is in the manual), that creates multiple Data Link paths to a single Application Layer session to accomplish that.  But it is recommended to have the different Data Link paths be different communications paths.

슈나이더 일렉트릭 Korea

자세히 알아보기

제품군

자세히 알아보기

제품군

도움이 필요하신가요?

제품 선택기

애플리케이션에 적합한 제품과 액세서리를 빠르고 쉽게 찾을 수 있습니다.

견적 받기

영업 관련하여 온라인으로 문의하시면 전문가가 연락드립니다.

구매처

해당 지역의 가장 가까운 슈나이더 일렉트릭 대리점을 쉽게 찾을 수 있습니다.

지원 센터

한 곳에서 모든 요구 사항에 대한 지원 리소스를 찾아보십시오.