오늘 무엇을 도와드릴까요?

EcoStruxure Power Operation (EPO) 2021: How to identify license is untrusted?

Issue
Suddenly Runtime Manager is throwing error message ‘software protection failure’ or runs in ‘Demo mode’ and stops after completing demo mode even though licenses are activated in EPO 2021 machine.
RTMUI
Environment
EcoStruxure Power Operation (EPO) 2021

Cause
Make sure that you have already activated the license in the 'Power Operation License Configuration Tool' and same is appearing in the tool.

To identify licenses are not getting detected, open PO Log folder and open syslog.dat file and you may observe the below logs (which is nothing, but FNE Provider is failing to supply the license)
SysLogs

This could be because the license state is untrusted, how to confirm the same?
Ans:
Go to Windows Logs > Applications and you may observe the below error –
WinEvent

Resolution
To fix the issue, follow the steps as per the exchange post to return licenses manually and then activate the licenses again –

  1. Close all the apps related to EPO (including PO License Configuration Tool) if they are already opened.
  2. Delete the files located in trusted storage “C:\ProgramData\Schneider Electric\Power Operation\v2021\License Manager\License” (it is better to copy to a safe location if you are unsure about the steps what you are doing.)
  3. To manually return the corrupt license contact SE Tech support team. (For SE internal users refer the exchange link for more details to raise a service now ticket)
  4. After a successful return, activate the licenses again.

슈나이더 일렉트릭 Korea

자세히 알아보기
제품군
자세히 알아보기
제품군
  • 제품 문서
  • 소프트웨어 다운로드
  • 제품 선택기
  • 제품 대체 및 교체
  • 지원 및 연락처 센터
  • 영업소 검색
  • 견적 받기
  • 슈나이더 일렉트릭 커뮤니티
  • 채용
  • 회사 소개
  • 부정 행위 보고
  • 접근성
  • 뉴스룸
  • 투자자
  • Ecostruxure
  • 작업 검색
  • 블로그
  • 개인정보 취급방침
  • 쿠키 공지
  • 사용 약관
  • Change your cookie settings