오늘 무엇을 도와드릴까요?

EcoStruxure Power Operation (EPO) 2021: Graphics editor crashes after duplicating a new component

Issue
When grouping several objects together as a component; after a few copies and pastes of the new component in the Graphics Editor, the application crashes with the following error message:

Graphics Editor – Unexpected Error
Object reference not set to an instance of an object

Error Message

The Graphics Editor application doesn't open again unless deleting the TGML file from the TGML folder.

Product Line
EcoStruxure Power Operation 2021 CU2/ CU3

Environment
Graphics Editor

Cause
When you copy and paste a new component, a new property called InstanceId is created under custom properties. InstanceID is unique but causes the application failure.

Resolution
The workaround is to delete the Instanceld property. Please right-click and delete the InstanceId line under Custom.

InstanceID Location

Note: The problem will be addressed in future updates.

슈나이더 일렉트릭 Korea

  • 제품 문서
  • 소프트웨어 다운로드
  • 제품 선택기
  • 제품 대체 및 교체
  • 지원 및 연락처 센터
  • 영업소 검색
  • 견적 받기
  • 슈나이더 일렉트릭 커뮤니티
  • 채용
  • 회사 소개
  • 부정 행위 보고
  • 접근성
  • 뉴스룸
  • 투자자
  • Ecostruxure
  • 작업 검색
  • 블로그
  • 개인정보 취급방침
  • 쿠키 공지
  • 사용 약관
  • Change your cookie settings