오늘 무엇을 도와드릴까요?

EcoStruxure Operator Terminal Expert - Backup and Restore recipe remotely.

Issue:

Is there any tool to backup and restore recipe file from HMI Target remotely (like Vijeo Data Manager does in Vijeo Designer) ?

Product Line:

EcoStruxure Operator Terminal Expert v3.5 SP1 and all previous versions.

Resolution:

No, there isn't any tool like data manager in Vijeo Designer.

For reference, FTP is not supported from the cyber security point of view, and R&D already had the plan to support FTPs in future version, then it should be able to backup and restore recipe file remotely. This feature has been implemented starting with version 4.0 of Operator Terminal Expert.

With previous versions, user can export related recipe file to USB memory stick.

In the Recipes - Control, set the Export/Import Data Location to USB Storage and define the folder Name.

Recipe Control setup for export/import to USB.

On the recipe screen, program some switches to execute the scripts to Export and import the recipes.

Recipe export/import scripts.

If this FAQ did not solve your issue, you can chat with us at chat with us or e-mail us at customer.services@se.com to create a case with our Technical Support Team.

If you are not located in North America, please contact your local Customer Care Center for assistance:

Support | Schneider Electric Global (se.com)

슈나이더 일렉트릭 Korea

자세히 알아보기
제품군
자세히 알아보기
제품군

도움이 필요하신가요?

도움이 필요하신가요?

제품 선택기

제품 선택기

애플리케이션에 적합한 제품과 액세서리를 빠르고 쉽게 찾을 수 있습니다.

견적 받기

견적 받기

영업 관련하여 온라인으로 문의하시면 전문가가 연락드립니다.

구매처

구매처

해당 지역의 가장 가까운 슈나이더 일렉트릭 대리점을 쉽게 찾을 수 있습니다.

지원 센터

지원 센터

한 곳에서 모든 요구 사항에 대한 지원 리소스를 찾아보십시오.

  • 제품 문서
  • 소프트웨어 다운로드
  • 제품 선택기
  • 제품 대체 및 교체
  • 지원 및 연락처 센터
  • 영업소 검색
  • 견적 받기
  • 슈나이더 일렉트릭 커뮤니티
  • 채용
  • 회사 소개
  • 부정 행위 보고
  • 접근성
  • 뉴스룸
  • 투자자
  • Ecostruxure
  • 작업 검색
  • 블로그
  • 개인정보 취급방침
  • 쿠키 공지
  • 사용 약관
  • Change your cookie settings