Topology not found error on Facility Expert web portal
Issue :
While associating a Panel server Gateway (PAS600 or PAS800) to EcoStruxure Facility Expert web portal, you may see an error message : “Your Topology is not found. please commission your panel server in EPC and try again” (refer screen shot below)

Tolopogy error

When this issue occurs:
This error occurs while commissioning the Panel server gateway (PAS600 or PAS800) to EcoStruxure Facility Expert web portal. Precisely when you are trying to associate the Panel server Serial ID to Facility Expert as shown in above screen shot.

Why this issue occurs:

Reason 1 :
When the topology shared by Panel server to cloud exceeds more than 256kb, you will see such kind of error Facility Expert. To check if this is the actual issue, you can check the diagnostic logs of panel server as shown in the below Picture 1:

Picture 1:
Logs
How to download the Panel server logs: Please refer the Panel server user guide to know more.
https://www.se.com/in/en/download/document/DOCA0172EN/

Picture 2:
Also refer the screen shot below Picture 2 from user guide:
Help

How to recover/avoid this issue:

When such error occurs, we recommend you to delete few devices commissioned in the panel server and perform again “Publish Topology”. Again download the Panel server logs and check for the similar messages give in Picture 1. If you do not see such message about topology file size exceeding 256kb, you can retry associating the Panel server serial ID with Facility Expert.
Is still issue persists, we recommend you to contact Schneider Electric country customer support

Reason 2:
This error may also occur when you have not published the Topology from Panel server and was trying to associate the Panel server Serial Id with Facility Expert.

How to recover/avoid this issue:

You need to first Connect the Panel server to cloud, then perform the "Publish Topology" and then later do the commissioning steps on Facility Expert .
So do remember to commission your Panel server first and then later Facility Expert to avoid such issues

슈나이더 일렉트릭 Korea

자세히 알아보기
제품군
제품군
자세히 알아보기
제품군
제품군
  • 제품 문서
  • 소프트웨어 다운로드
  • 제품 선택기
  • 제품 대체 및 교체
  • 지원 및 연락처 센터
  • 영업소 검색
  • 견적 받기
  • 슈나이더 일렉트릭 커뮤니티
  • 채용
  • 회사 소개
  • 부정 행위 보고
  • 접근성
  • 뉴스룸
  • 투자자
  • Ecostruxure
  • 작업 검색
  • 블로그
  • 개인정보 취급방침
  • 쿠키 공지
  • 사용 약관
  • Change your cookie settings