Why my application does not build when I import some DFB from another application (older version of Control Expert) with same DDT structure assigned?
Possible Cause:
The DDT structure in the new application might differ from the one in the older application. This can happen when types are automatically generated by DTMs, as DTM evolutions may introduce changes.
Additionally, the DDT structure could include hidden variables, causing Control Expert to detect a mismatch between the types and raise an error.
To confirm whether you encounter the same issue:
- Export both DDTs in .XSY format (the one generated from the new DFB and the one already present in the application).
- Open the exported files in Notepad and compare the variable types and names to ensure they are identical.
Example:
If the comparison shows differences:
Update the DDT type used in the DFB so that it matches the one already defined in the application.
Recommendation:
Avoid using DDTs that are automatically generated by DTMs within a DFB, as these can lead to inconsistencies due to DTM evolutions.
게시 대상: 슈나이더 일렉트릭 Korea
도움이 필요하신가요?
제품 선택기
애플리케이션에 적합한 제품과 액세서리를 빠르고 쉽게 찾을 수 있습니다.
견적 받기
영업 관련하여 온라인으로 문의하시면 전문가가 연락드립니다.
구매처
해당 지역의 가장 가까운 슈나이더 일렉트릭 대리점을 쉽게 찾을 수 있습니다.
지원 센터
한 곳에서 모든 요구 사항에 대한 지원 리소스를 찾아보십시오.