How can you setup a custom display to show temperature or pressure as the PID setpoint on the ATV212 Drives?
Issue:
Setting up custom display to show pressure or temperature values as the PID setpoint on the ATV212 Drives.
Product Line:
ATV212
Environment:
All
Cause:
Custom display
Resolution:
Example below will be to display 32F to 122F degrees temperature on the display as the PID setpoint.
Let's start with the Lowest value to set which is 32F.
32F divided by 1.5 (F702) = 21.3333
F706=21.33
Set now look at the Highest value to set which is 122F.
122F minus 32F= 90F minus F706 value of 21.33= 68.67
68.67X 1.5 (F702) =103.00+ F706 value 21.33= 124F Your highest value you can set.
F701- 1 default.
F702= 1.5
F703=1
F705=1
F706= 21.35
FNOD=3 PID keypad setpoint
F360= 1VIA
V380= PID inverse set to yes for temp PID
Now using up and down buttons your setpoint is between 32F and 124F.
Note it will not show any units like F or Psi only the number.
게시 대상: 슈나이더 일렉트릭 Korea




도움이 필요하신가요?
제품 선택기
애플리케이션에 적합한 제품과 액세서리를 빠르고 쉽게 찾을 수 있습니다.
견적 받기
영업 관련하여 온라인으로 문의하시면 전문가가 연락드립니다.
구매처
해당 지역의 가장 가까운 슈나이더 일렉트릭 대리점을 쉽게 찾을 수 있습니다.
지원 센터
한 곳에서 모든 요구 사항에 대한 지원 리소스를 찾아보십시오.