오늘 무엇을 도와드릴까요?
How do you wire a smoke detector/firestat on an ATV212?
1. Wire the smoke detector between R/RES and P24.
2. Program the following:
If wired between R and P24,
F--- >
F110 = 0
F112 = 1
If wired between RES and P24,
F--- >
F110 = 0
F113 = 1
게시 대상: 슈나이더 일렉트릭 Korea