How do you keep the security settings saved on the HMI after a new download?
Issue:
When downloading again to an HMI, how to keep the security settings that were previously downloaded.
Product Line:
Vijeo Designer 6.2
Resolution:
There is a way for you to keep the user's setting saved on your HMI even after downloading again the project into the HMI. You just have to make sure to do 2 things:
1. On your Vijeo Designer project please go to Target -> General and please make sure to check the checkbox "Preserve Run-Time Data".

2. Later, when you go to download to the HMI, please make sure to leave UNCHECKED the checkbox "Delete All Runtime". If you do select this option, any time you make a security setting change it will override the existing security settings on the HMI. If you do not check the checkbox, your settings do not take effect.
This "Delete All Runtime" option may appear more than one time, please make sure to always leave it UNCHECKED.
If this FAQ did not solve your issue, you can chat with us at chat with us or e-mail us at customer.services@se.com to create a case with our Technical Support Team.
If you are not located in North America, please contact your local Customer Care Center for assistance:
Support | Schneider Electric Global (se.com)
When downloading again to an HMI, how to keep the security settings that were previously downloaded.
Product Line:
Vijeo Designer 6.2
Resolution:
There is a way for you to keep the user's setting saved on your HMI even after downloading again the project into the HMI. You just have to make sure to do 2 things:
1. On your Vijeo Designer project please go to Target -> General and please make sure to check the checkbox "Preserve Run-Time Data".
2. Later, when you go to download to the HMI, please make sure to leave UNCHECKED the checkbox "Delete All Runtime". If you do select this option, any time you make a security setting change it will override the existing security settings on the HMI. If you do not check the checkbox, your settings do not take effect.
This "Delete All Runtime" option may appear more than one time, please make sure to always leave it UNCHECKED.
If this FAQ did not solve your issue, you can chat with us at chat with us or e-mail us at customer.services@se.com to create a case with our Technical Support Team.
If you are not located in North America, please contact your local Customer Care Center for assistance:
Support | Schneider Electric Global (se.com)
게시 대상: 슈나이더 일렉트릭 Korea


도움이 필요하신가요?
제품 선택기
애플리케이션에 적합한 제품과 액세서리를 빠르고 쉽게 찾을 수 있습니다.
견적 받기
영업 관련하여 온라인으로 문의하시면 전문가가 연락드립니다.
구매처
해당 지역의 가장 가까운 슈나이더 일렉트릭 대리점을 쉽게 찾을 수 있습니다.
지원 센터
한 곳에서 모든 요구 사항에 대한 지원 리소스를 찾아보십시오.