브랜드

슈나이더 일렉트릭 코리아 웹사이트에 방문해 주셔서 감사합니다.

슈나이더 일렉트릭 코리아 웹사이트 방문자 분들 모두 환영합니다.
		
오늘 무엇을 도와드릴까요?
How to update M580 CPU NTP time via BMENOC0321 module

The CPU time can be synchronized with the NTP time provided by the BMENOC0321 module installed on the same rack. This process is not automatic and requires explicit programming, by following these steps:


1- Enable the "Network Time Service" on the DTM of the BMENOC0321:

BMENOC0321 DTM

2- Open the "Network Time Service " in the service list and put the NTP remote server IP address. You can customise the Polling period, the Time Zone option, etc:


Network Time Service configuration

3- Import the attached program section in your program:

Import section

4- Configure the DFB by putting the module rack position and its IP address:

DFB configuration

5- Use the "Enable" pin to activate the DFB and the Sync_PLC to enable the time synchronization.

6- Enable "Dynamic Arrays" variables in the project settings:

Project settings

The CPU time will be updated after enabling the DFB (via its "Enable" input) AND sending a commande into Sync_PLC input :

Animated DFB

Note: There is no need to enable the CPU’s ‘NTP client’ service.

Best Regards.

슈나이더 일렉트릭 Korea

첨부 파일
NTP_NOC0321.7z [1.82 KB]
자세히 알아보기
제품군
자세히 알아보기
제품군
  • 제품 문서
  • 소프트웨어 다운로드
  • 제품 선택기
  • 제품 대체 및 교체
  • 지원 및 연락처 센터
  • 영업소 검색
  • 견적 받기
  • 슈나이더 일렉트릭 커뮤니티
  • 채용
  • 회사 소개
  • 부정 행위 보고
  • 접근성
  • 뉴스룸
  • 투자자
  • Ecostruxure
  • 작업 검색
  • 블로그
  • 개인정보 취급방침
  • 쿠키 공지
  • 사용 약관
  • Change your cookie settings