브랜드

슈나이더 일렉트릭 코리아 웹사이트에 방문해 주셔서 감사합니다.

슈나이더 일렉트릭 코리아 웹사이트 방문자 분들 모두 환영합니다.
		
오늘 무엇을 도와드릴까요?
How to realize the secure authentication link for M340 PLC
  1. Issue
Customer needs technical support on how to realize the secure authentication for M340 PLC?
  1. Environment
M340 Processor with Firmware version 3.60
Control Expert V16.0
M340 Application version 3.60
  1. Description
Update the M340 processor firmware to V3.60 (or use the SV3.60 M340 processor), program with Control Expert V16.0 and M340 Application version 3.60.
Then Select “Protected Engineering Link” in M340 CPU configuration,
PEL

and Set application password in Project Properties à Project & Control Protection.
CPW

In this environment, build the project, connect to M340 CPU, and download the configuration & applications after which the secure authentication mode is established in M340.

Note: this “Protected Engineering Link” option is enabled by default in Control Expert V16.0 with M340 Application version 3.60. It may cause initial connection time between Control Expert and M340 controller due to the cyber security inspection mechanism to be established.

Workaround: Deselect the “Protected Engineering Link” mode, or change the Mast task to “Periodic” & “>20ms.


슈나이더 일렉트릭 Korea

자세히 알아보기
제품군
자세히 알아보기
제품군
  • 제품 문서
  • 소프트웨어 다운로드
  • 제품 선택기
  • 제품 대체 및 교체
  • 지원 및 연락처 센터
  • 영업소 검색
  • 견적 받기
  • 슈나이더 일렉트릭 커뮤니티
  • 채용
  • 회사 소개
  • 부정 행위 보고
  • 접근성
  • 뉴스룸
  • 투자자
  • Ecostruxure
  • 작업 검색
  • 블로그
  • 개인정보 취급방침
  • 쿠키 공지
  • 사용 약관
  • Change your cookie settings