Offline activation of the PowerChute Network Shutdown license failed with the error “Request is tampered, error code: ERROR:22; Non-XML input was encountered where XML input is expected.”

Issue:
Offline activation of the PowerChute Network Shutdown license failed with the error “Request is tampered, error code: ERROR:22; Non-XML input was encountered where XML input is expected.”
Offline activation failed error

Product:
PowerChute Network Shutdown version 5

Environment:
All supported OS

Cause:
Adding the Activation code incorrectly in Schneider Exchange.

Solution:
See the attached PDF for full instructions.

For instructions on how to activate a license off-line see Schneider Electric FAQ000271561. Or see the attached PowerChute 5.2 VMware Users Guide starting on page 290.

슈나이더 일렉트릭 Korea

첨부 파일
Offline activation of the PowerChute Network Shutdown license failed with the error.pdf [293.21 KB]
Offline activation of the PowerChute Network Shutdown license failed with the error.pdf [287.92 KB]
PowerChute 5.2 VMware Users Guide.pdf [14.74 MB]