오늘 무엇을 도와드릴까요?

Why does my Smart UPS Modular Ultra show "Unknown UPS internal error [3B7D-00A0]" on the display?

Issue:

After performing a UPS Firmware upgrade, removing and installing the Intelligence Modules, or when the UPS is booting up from a brains dead, you may see the display show "Unknown UPS internal error [3B7D-00A0]".


Product Line:

Smart UPS Modular Ultra


Environment:

All models, all serial numbers


Resolution:

This specific message occurs when the Redundant Intelligence Module (RIM) is initializing after power up. In later versions of the NMC/Display firmware, the messaging is changed to "RIM initializing, Do not remove MIM".  Please upgrade the NMC/Display firmware to SUCAN 2.5.1.3 to see update messaging.   You can upgrade the firmware by following this FAQ: https://www.apc.com/us/en/faqs/FAQ000261841/

슈나이더 일렉트릭 Korea

자세히 알아보기
제품군
자세히 알아보기
제품군
  • 제품 문서
  • 소프트웨어 다운로드
  • 제품 선택기
  • 제품 대체 및 교체
  • 지원 및 연락처 센터
  • 영업소 검색
  • 견적 받기
  • 슈나이더 일렉트릭 커뮤니티
  • 채용
  • 회사 소개
  • 부정 행위 보고
  • 접근성
  • 뉴스룸
  • 투자자
  • Ecostruxure
  • 작업 검색
  • 블로그
  • 개인정보 취급방침
  • 쿠키 공지
  • 사용 약관
  • Change your cookie settings