오늘 무엇을 도와드릴까요?
What's the signal wires size and specifications for SELV and Non-SELV?
Product line:
Three Phase UPS, Galaxy V Series
Environment:
GVS, GVM, GVL, GVX
Resolution:
All Class 2/SELV signal cables shall be double insulated/jacket cable and minimum rated for 30 VDC. All non-Class 2/non-SELV signal cables shall be double insulated/jacket cable and minimum rated for 600 VAC.

Three Phase UPS, Galaxy V Series
Environment:
GVS, GVM, GVL, GVX
Resolution:
All Class 2/SELV signal cables shall be double insulated/jacket cable and minimum rated for 30 VDC. All non-Class 2/non-SELV signal cables shall be double insulated/jacket cable and minimum rated for 600 VAC.
게시 대상: 슈나이더 일렉트릭 Korea