브랜드

Impact-Company-Logo-English Black-01-177x54

슈나이더 일렉트릭 코리아 웹사이트에 방문해 주셔서 감사합니다.

슈나이더 일렉트릭 코리아 웹사이트 방문자 분들 모두 환영합니다.
		
오늘 무엇을 도와드릴까요?
How to Perform a Logic Reset or "Brain Dead" on a Smart-UPS Ultra 5-10kW?

Article available in these languages: 프랑스어

Issue:
This document explains how to perform the Brain Dead procedure on a Smart-UPS Ultra 5-10kW

Product Line:
Smart-UPS Ultra 5-10kW models: SRTL5KRM2UI, SRTL5KRM2UT, SRTL8KRM4UI, SRTL8KRM4UT, SRTL10KRM4UI, SRTL10KRM4UT

Cause:
The Brain Dead procedure performs a reset of the UPS microprocessor. This is useful for basic troubleshooting to attempt to clear any alarms. It does not however reset saved preferences.

Resolution:

  1. Turn off any connected load.
  2. Turn off the UPS using the LCD Display, and disconnect the AC input.
    • For hardwired units, refer to the User Manual - Deenergizing safety.
  3. Turn off the internal battery module using the Battery On/Off switch (located on the front of each battery module)
    • Turn off the battery modules using Battery On/Off switch in any external battery packs connected to the UPS.
  4. Reconnect the internal and any external batteries, reconnect AC input, and turn the UPS on using the LCD Display.

Note: Refer to the UPS Operation Manual for how to turn the UPS and the batteries on or off.

슈나이더 일렉트릭 Korea

자세히 알아보기
제품군
자세히 알아보기
제품군
  • 제품 문서
  • 소프트웨어 다운로드
  • 제품 선택기
  • 제품 대체 및 교체
  • 지원 및 연락처 센터
  • 영업소 검색
  • 견적 받기
  • 슈나이더 일렉트릭 커뮤니티
  • 채용
  • 회사 소개
  • 부정 행위 보고
  • 접근성
  • 뉴스룸
  • 투자자
  • Ecostruxure
  • 작업 검색
  • 블로그
  • 개인정보 취급방침
  • 쿠키 공지
  • 사용 약관
  • Change your cookie settings