Machine SCADA Expert, Como Box Object and Array Tags.
Issue:
Combo Box object using an Array Tag as the Data Source:
When the screen is viewed on the runtime server, the Combo Box displays the selection list correctly.
But when viewed on a Thin Client, the Combo Box only displays the first element of the list or Array Tag.
Product Line:
EcoStruxure Machine SCADA Expert (all versions)
Resolution:
In the Help document of EcoStruxure Machine Expert, under the Combo Box object , for the Data Source Type: Array tag,
It is mentioned: This type is not supported in project screens that are viewed through Mobile Access. (This includes Thin Clients.)
It is needed to use another Data Source Type.
If this FAQ did not solve your issue, you can chat with us at chat with us or e-mail us at customer.services@se.com to create a case with our Technical Support Team.
If you are not located in North America, please contact your local Customer Care Center for assistance: Support | Schneider Electric Global (se.com)